Field Measurement and Data-Driven Modeling of a Photovoltaic/Thermal and Air-Source Dual-Source Heat Pump System in Dalian, China

Document Type

Article

Publication Date

3-1-2026

Abstract

Dual-source heat pump systems combining photovoltaic-thermal (PVT) and air-source technologies have attracted considerable research interest due to their energy complementarity. Based on the climatic characteristics of the Dalian region, this study conducted field measurements and data analysis on a developed dual-source heat pump system incorporating three adaptive operational modes: (1) PVT mode, (2) PVT/air dual-source mode, and (3) photovoltaic (PV)/air-source mode. Compared to Mode (3), Mode (1) achieves a 5.76% higher heating capacity and an 11.56% greater electrical efficiency. Meanwhile, Mode (2) demonstrates a 12.23% increase in heating capacity, and a 9.14% improvement in electrical efficiency relative to Mode (3). A data-driven methodology is provided to quantify the system’s evaporation temperature, the thermal efficiency of PVT mode, and the coefficient of performance (COP) of the PVT heat pump. The economic assessment demonstrates that the proposed dual-source heat pump system achieves a heating cost as low as RMB 0.1125/kWh and a payback period of 6.4 years, indicating favorable economic benefits. This study provides fundamental data and computational methods for the optimized operation of the PVT/air dual-source heat pump.

Keywords

air-source, dual-source heat pump, heating performance, PVT

Publication Title

Buildings

ISSN

2075-5309

DOI

10.3390/buildings16061242

Volume

16

Issue

6

Publisher

Multidisciplinary Digital Publishing Institute (MDPI)

Share