Abstract
This paper presents an adaptive thermal comfort model study in the tropical country of Malaysia. A number of researchers have been interested in applying the adaptive thermal comfort model to different climates throughout the world, but so far no study has been performed in Malaysia. For the use as a thermal comfort model, which better applies to hot and humid climates, the adaptive thermal comfort model was developed as part of this research by using the collected results from a large field study in six lecture halls with 178 students. The relationship between the operative temperature and behavioral adaptations was determined. In the developed adaptive model, the acceptable indoor neutral temperatures lay within the range of 23.9-26.0oC, with outdoor temperatures ranging between 27.0-34.6oC. The most comfortable temperature for students in lecture hall was 25.7oC.
Keywords
Hot and humid, Lecture halls, Neutral temperature, Adaptive thermal comfort model.
Divisions
fac_eng
Event Title
International Conference on Air Pollution and Control
Event Location
Paris, France
Event Dates
23-24 Feb 2015